Regulation BEFORE repealed by BC Reg 198/2005, effective September 30, 2005.
B.C. Reg. 290/2004 M251/2004 | Deposited June 24, 2004 effective January 1, 2005 |
Local Government Act
Water Conservation Plumbing Regulation
Maximum flow rates
1 The flow rates of fittings that supply water to plumbing fixtures must not exceed the maximum flow rate at the test pressures listed for that fitting in the following table, titled Maximum Flow Rates for Water Supply Fittings, for Group C, D and E occupancies as described in the British Columbia Building Code.
Maximum Flow Rates for Water Supply Fittings | ||
Fittings | Maximum Flow (L/min) | Test Pressure (kPa) |
Lavatory Faucet | 8.3 | 415 |
Kitchen Faucet | 8.3 | 415 |
Shower Head | 9.5 | 550 |
Maximum water consumption
2 (1) The flush cycle for the installation of a new water closet or urinal provided in a Group C, D or E occupancy, as described in the British Columbia Building Code, must not exceed the flush cycle listed for that fixture in the following table, titled Maximum Flush Cycle Table 1.
Maximum Flush Cycle Table 1 | |
Fixture | Litres |
Water Closet (Tank Type) | 13.25 |
Water Closet (Direct Flush) | 13.25 |
Urinal (Tank Type) | 5.7 |
Urinal (Direct Flush) | 5.7 |
(2) Despite the requirements of subsection (1), within the geographic locations listed below the installation of a new water closet or urinal in all occupancy classifications described in the British Columbia Building Code must not exceed the flush cycle listed for that fixture in the following table, titled Maximum Flush Cycle Table 2.
Geographic location
— all areas within the Capital Regional District
Maximum Flush Cycle Table 2 | |
Fixture | Litres |
Water Closet (Tank Type) | 6.0 |
Water Closet (Direct Flush) | 6.0 |
Urinal (Tank Type) | 5.7 |
Urinal (Direct Flush) | 5.7 |
Identification
3 (1) Watersaver water closets must be marked with
(a) WS,
(b) 13.25 LPF,
(c) WS/13.25 LPF, or
(d) x LPF which indicates the actual confirmed test value (in litres per flush) and where x is equal to or less than 13.25.
(2) Low Consumption water closets must be marked with
(a) LC,
(b) 6 LPF,
(c) LC/6 LPF, or
(d) x LPF which indicates the actual confirmed test value (in litres per flush) and where x is equal to or less than 6.
Flush tanks
4 The water supply to urinal flush tanks equipped for automatic flushing must be controlled with a timing device in order to limit operation to the time period during which the building is normally occupied.
Note: this regulation replaces B.C. Reg. 294/98.
[Provisions of the Local Government Act, R.S.B.C. 1996, c. 323, relevant to the enactment of this regulation: section 692]